Product Description
Application
Used for overhead power transmission and distribution lines of AC rated voltage up to and including 1kV or rated voltage 10kV.
Standard
Rated voltages up to and including 1KV aerial insulated cable implement the standard GB/T 12527, ANSI/ICEA S-76-474, NFC 33029, BS 7870-5, DINVDE0276-626-A1, AS3560-1. Rated voltage 10KV aerial insulated cable implement the standard GB/T 14049.
Application Properties
Rated voltage is up to and including 1KV, 10KV.
The conductor long-term maximum working temperature:PVC and PE insulation should not exceed 70 °C,XLPE insulation should not exceed 90°C.
During short circuit (maximum permanent time is not more than 5 seconds), the maximum temperature of cable conductor : XLPE insulation 250°C, High-density polyethylene insulation 150°C;
When laying the cable, minimum ambient temperature of laying should not be lower than -20°C.
The minimum bending radius:≥20 (D+d)±5%mm, D is the cable overall diameter, d is the conductor diameter.
Product Performance
Conductor DC resistance ( at 20°C ) conform to the stipulation of GB/T 3956-2008.
AC Volage Test:3.5kV,lasting for 5min,without breakdown.
Type and Description
Overhead Insulated Power Cable of rated voltage up to and including 1kV.
Type | Description | Main Application |
JKV | Copper conductor PVC insulated overhead cable with rated voltage 1KV. | Overhead fixed installation, Lead household line. |
JKLV | Aluminum conductor PVC insulated overhead cable with rated voltage 1KV. |
JKLHV | Aluminum alloy conductor PVC insulated overhead cable with rated voltage 1KV. |
JKY | Copper conductor PE insulated overhead cable with rated voltage 1KV. |
JKLY | Aluminum conductor PE insulated overhead cable with rated voltage 1KV. |
JKLHY | Aluminum alloy conductor PE insulated overhead cable with rated voltage 1KV. |
JKLGY | ACSR conductor PE insulated overhead cable with rated voltage 1KV. |
JKYJ | Copper conductor XLPE insulated overhead cable with rated voltage 1KV. |
JKLYJ | Aluminum conductor XLPE insulated overhead cable with rated voltage 1KV. |
JKLHYJ | Aluminum alloy conductor XLPE insulated overhead cable with rated voltage 1KV. |
JKLGYJ | ACSR conductor PE insulated overhead cable with rated voltage 1KV. |
Specification
Overhead Insulated Power Cable of Rated Voltages up to and Including 1 kv.
Type | Core | Main line core nominal area mm2 |
JKV,JKLV,JKLHV,JKY, JKLY,JKLHY,JKLGY,JKYJ, JKLYJ,JKLHYJ,JKLGYJ | 1 | 10~400 |
2,4 | 10~120 |
JKLV,JKLY,JKLYJ | 3+k | 10~120 |
K is the no of neutral core or load bearing line core. According to engineering requirements, to select one to go with the main core. (A) represents steel stranded neutral core. (B) represents aluminium alloy stranded neutral core. |
Triplex Aluminum Service Drop Cable
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ |
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY |
|
AAAC 6201 ALLOY FULL NEUTRAL MESSENGER |
|
Minex | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 101 | 101 | 85 | 70 |
Hippa | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 107 | 107 | 85 | 70 |
Prawn | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 152 | 152 | 115 | 90 |
Barnacle | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 160 | 160 | 115 | 90 |
Shrimp | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 243 | 243 | 150 | 120 |
Gammarus | 1/0 | 7 | 60 | 1/0 | 123.3 | 7 | 4460 | 390 | 390 | 205 | 160 |
Leda | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 384 | 384 | 205 | 160 |
Dunganese | 2/0 | 7 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
Cyclops | 2/0 | 11 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
Flustra | 3/0 | 17 | 60 | 3/0 | 195.7 | 7 | 6790 | 587 | 587 | 275 | 215 |
Lepas | 4/0 | 18 | 60 | 4/0 | 246.9 | 7 | 8560 | 728 | 728 | 315 | 245 |
|
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ |
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY |
|
AAAC 6201 ALLOY REDUCED NEUTRAL MESSANGER |
Artemia | 4 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 135 | 135 | 115 | 90 |
Crab | 4 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 143 | 143 | 115 | 90 |
Solaster | 2 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 216 | 216 | 150 | 120 |
Sandcrab | 1/0 | 7 | 60 | 2 | 77.47 | 7 | 2800 | 347 | 347 | 205 | 160 |
Echinus | 1/0 | 9 | 60 | 2 | 77.47 | 7 | 2800 | 341 | 341 | 205 | 160 |
Crayfish | 2/0 | 7/w | 60 mls | 2/0 | -- | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
Sipho | 2/0 | 7/w | 60 mls | 2/0 | -- | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
Fulgar | 3/0 | 17 | 60 | 1/0 | 123.3 | 7 | 4460 | 519 | 519 | 275 | 215 |
Arca | 4/0 | 18 | 60 | 2/0 | 155.4 | 7 | 5390 | 643 | 643 | 315 | 245 |
|
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+............... |
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY |
|
AAC NEUTRAL-MESSENGER |
Haiotis | 6 | 7/w | 45 mls | 6 | 7 | 563 | 109.1 | 101.6 | 85 Amps | 70 Amps |
Patella | 6 | 7 | 45 | 6 | 7 | 563 | 103 | 103 | 85 | 70 |
Fusus | 4 | 7/w | 45 mls | 4 | 7 | 881 | 161.8 | 151.7 | 115 Amps | 90 Amps |
Oyster | 4 | 7 | 45 | 4 | 7 | 881 | 154 | 154 | 115 | 90 |
Clam | 2 | 7 | 45 | 2 | 7 | 1350 | 233 | 233 | 150 | 120 |
Murex | 1/0 | 7 | 60 | 1/0 | 7 | 1990 | 374 | 374 | 205 | 160 |
Purpura | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 368 | 368 | 205 | 160 |
Nassa | 2/0 | 7 | 60 | 2/0 | 7 | 2510 | 462 | 462 | 235 | 185 |
Melita | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 562 | 562 | 275 | 215 |
Portunus | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 696 | 696 | 315 | 245 |
Nannynose | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 1118 | 1118 | 420 | 325 |
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ |
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY |
ASCR NEUTRAL-MESSENGER |
Paludina | 6 | 1 | 45 | 6 | 6/1 | 1190 | 109 | 109 | 85 | 70 |
Voluta | 6 | 7 | 45 | 6 | 6/1 | 1190 | 114 | 114 | 86 | 70 |
Whelk | 4 | 1 | 45 | 4 | 6/1 | 1860 | -- | 164 | 115 | 90 |
Periwinkle | 4 | 7 | 45 | 4 | 6/1 | 1860 | 172 | 172 | 115 | 90 |
Conch | 2 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
Neritina | 1/0 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
Cenia | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 414 | 414 | 205 | 160 |
Runcina | 2/0 | 7 | 60 | 2/0 | 6/1 | 5310 | 520 | 520 | 235 | 185 |
Triton | 2/0 | 11 | 60 | 2/0 | 6/1 | 5310 | 512 | 512 | 235 | 185 |
Mursia | 3/0 | 17 | 60 | 3/0 | 6/1 | 6620 | 635 | 635 | 275 | 215 |
Zuzara | 4/0 | 18 | 60 | 4/0 | 6/1 | 8350 | 789 | 789 | 315 | 245 |
Limpet | 336.4 | 19 | 80 | 336.4 | 18/1 | 8680 | 1167 | 1167 | 420 | 325 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ |
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY |
ASCR REDUCED NEUTRAL-MESSENGER |
Scallop | 4 | 1 | 45 | 6 | 6/1 | 1190 | -- | 142 | 115 | 90 |
Strombus | 4 | 7 | 45 | 6 | 6/1 | 1190 | 151 | 151 | 115 | 90 |
Cockle | 2 | 7 | 45 | 4 | 6/1 | 1190 | 220 | 220 | 150 | 120 |
Janthina | 1/0 | 7 | 60 | 2 | 6/1 | 2853 | 366 | 366 | 205 | 160 |
Ranella | 1/0 | 9 | 60 | 2 | 6/1 | 2853 | 360 | 360 | 205 | 160 |
Cavolinia | 2/0 | 7 | 60 | 1 | 6/1 | 3550 | 453 | 453 | 235 | 185 |
Clio | 2/0 | 11 | 60 | 1 | 6/1 | 3550 | 444 | 444 | 235 | 185 |
Sanddollar | 3/0 | 19/w | 60 mls | 1/0 | 6/1 | 4380 | 565 | 552 | 275 Amps | 215 Amps |
Aega | 3/0 | 17 | 60 | 1/0 | 6/1 | 4380 | 549 | 549 | 275 | 215 |
Cuttlefish | 4/0 | 19/w | 60 mls | 2/0 | 6/1 | 5310 | 699 | 684 | 315 Amps | 245 Amps |
Cerapus | 4/0 | 18 | 60 | 2/0 | 6/1 | 5310 | 681 | 681 | 315 | 245 |
Cowery | 336.4 | 19 | 80 mls | 336/4 | 18/1 | 8680 | 1209 | 1167 | 420 Amps | 325 Amps |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
Address:
Shijiawan Industrial Estate, Guxian Town, Yanshi City, Luoyang, Henan, China
Business Type:
Manufacturer/Factory, Trading Company
Business Range:
Electrical & Electronics
Management System Certification:
ISO 9001, ISO 14001
Company Introduction:
Huatong Cable Inc. has made outstanding contribution to STATE GRID, China SOUTH POWER GRID and the construction of domestic and foreign power market since foundation in 1993. The honors should be attributed to more than 20 years of constant R&D, market service and strong will.
Huatong Cable Inc. has set up overhead conductor division, power cable division and division of wire and cable for equipment. The division respectively takes charge of manufacture and marketing of overhead conductor, power cable and wire and cable for equipment. In 2002, our company set up the cable industry design and technology R&D department, providing technical support for product design and production. Our company makes independent innovation, and seeks cooperation with academic institutions including Shanghai Electric Cable Research Institute and China Electric Power Research Institute so as to meet the customized demands of customers and production needs of special cable. Now our company owns 25 exclusive rights to use trademark registered at home and abroad and 14 independent intellectual property patents. ACSR-720/50 aluminum cable steel reinforced has passed the technical appraisal of China Electricity Council. 500KV or above extra-high voltage conductor was put into production, came into service and had good operation record.
In 2013, Huatong Brand was awarded WELL KNOWN MARK OF China by the Trademark Office of the State Administration of Industry and Commerce, enjoying a high reputation in domestic market. The honor and legal status reflect the recognition of customers and support of the State Administration of Industry and Commerce. It is the only enterprise in cable industry in Henan that was awarded WELL KNOWN MARK OF China and Huatong brand will serve the society in the future.